REVIEWERS
INITIALS AT:
ELECTRICAL
100%
35%
Interior Systems:
1.
a.
All electrical characteristics of
circuits (phase , voltage and number
of wires) have been calculated and
sizes shown on drawings . . . . . . . . .
b.
All lighting and power loads,
especially for special equipment
have been considered and connections
indicated . . . . . . . . . . . . . . . . . . .
Type of wiring system and size of
C.
conduits indicated . . . . . . . . . . . . . .
Selection and setting of protective
d.
devices is properly coordinated . . . . . .
e.
Short circuit duty requirement
considered and interrupting capacity
ratings are indicated for all new
circuit protective devices . . . . . .
Type and arrangement of telephone,
f.
signal, security and fire alarm
systems is satisfactory. . . . . . . .
g.
Explosion proof equipment shown if
required . . . . . . . . . . . . . . . . . . . . . . . . . . . .
New transformer requirements are
h.
indicated . . . . . . . . . . . . . . . . . . . . . . . . . . .
Provisions are made for cut over to
i.
new system . . . . . . . . . . . . . . . . . . . . . . . . . .
Outages and temporary power during
j.
construction have been coordinated
with customer . . . . . . . . . . . . . . .
k.
All panelboards are properly
coordinated with electrical riser
diagram and circuit numbers are
shown . . . . . . . . . . . . . . . . . . .
l.
All panelboards are properly shown
on panelboard schedule and sequence
of cutover showing when critical . . . .