AUDIBLE ALARM DEVICES:  Audible alarm devices shall be horns or
electronic sound generators.  Use approximately 3,000 feet square per audible
alarm device in open areas.  Visual alarm indicators shall be pulse or strobe
type.  Provide audiovisual alarms where occupancy is subject to higher than
normal noise or for use by handicapped personnel.
SUBMITTALS:  Contractor's submittal requirements in specifications
1.10
shall include a layout plan of all fire alarm devices and conduit runs in
addition to scaled shop drawings required by NAVFAC Guide Specification
16722.  (Minimum size drawings that are acceptable is 1/8 scale.)
RADIO FIRE ALARM TRANSMITTERS AND/OR TRANSMITTER/INTERFACE PANEL:
1.11
Where radio fire alarm transmitters are required, the designer shall provide a
specification section for them.  Careful consideration is necessary for
placement of radio transmitters and antenna (obstructions, maximum height
allowances, etc.).  Place transmitters in accessible, visible, and well
travelled exterior locations.  Combination transmitter/interface panels can be
used.
1.12
ELEVATORS:  Smoke detectors and/or heat detectors for elevator
machine rooms and hoistway areas shall be controlled by the building's 24 Vdc
FACP.