3.3.8.3 Regulator Bypassing Equipment. Equipment used to bypass regulators includes
circuit breakers, interlocking switches, and cutouts with disconnecting blades. A convenient
switching device is the regulator bypass switch, which includes switches B, C, and D of Figure
3-10, as an integral unit. When the regulator bypass switch is operated, the correct switching
sequence occurs.