Quantcast Figure 3-8. Steam Trap Inspection Equipment

Share on Google+Share on FacebookShare on LinkedInShare on TwitterShare on DiggShare on Stumble Upon
Custom Search
 
  
 


TABLE 3-1.  Normal Pipe Temperatures at
Various Operating Pressures
Pipe Surface
Steam
Temperature Range
Pressure
(F)
(psig)
212
0 (atmosphere)
225-238
15
245-260
30
305-320
100
330-350
150
350-370
200
415-435
450
435-465
600
FIGURE 3-8.
Steam Trap Inspection Equipment