REVIEWERS
INITIALS AT:
ELECTRICAL (Cont`d)
100%
35%
Special coordination requirements
b.
are noted in specifications.........
Government furnished equipment, new
c.
and/or relocated is identified......
d.
Antenna requirements - foundations,
grounding, aircraft obstruction
markings, mounting methods are
complied with . . . . . . . . . . . . . . . . . . . . . . .
e.
grounding provisions are adequate...
Radio frequency shielding requirements
f.
are indicated . . . . . . . . . . . . . . . . . . . . . . .
g.
Wired circuits for voice, remote
control, etc. are shown.............
Emergency and/or no-break power
h.
supply requirements are adequate....
Security requirements are met.......
i.
Azimuth of coverage and special
j.
precautions indicated for radar
installations . . . . . . . . . . . . . . . . .
General:
5.
a.
Standard title block format is shown.
b.
Drawing, contract, work request and
special numbers, when applicable,
are shown . . . . . . . . . . . . . . . . . . . . . . . . . . .
c.
Location map, scale(s), abbreviations
and legend with symbol explanations are
shown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
d.
All drawing notes and wording are
checked for proper spelling and
English usage....................
e.
Locations of all existing walls,
windows, doors, equipment, systems,
etc. shown have been field checked
and verified correct................