REVIEWERS
FIRE PROTECTION
INITIALS AT:
35%
100%
1.
Existing buildings within 100 ft of
proposed facility, including height and
type of construction, are shown..........
2.
Existing fire hydrants within 400 ft of
proposed facility are shown.............
3.
Flow tests made on main at point of
connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.
Automatic sprinkler system: CO2 Hose
Reel System required, and are properly
shown in each room . . . . . . . . . . . . . . . . . . . . . .
5.
Automatic/Manual fire alarm system
requirements  indicated . . . . . . . . . . . . . . . . . .
6.
Construction type considered: Combustible,
noncombustible,  fire  resistant..........
7.
Proper interior finishing materials and
insulation are used . . . . . . . . . . . . . . . . . . . . .
8.
Fire separation requirements; and fire
walls have been considered . . . . . . . . . . . . . .
Exits are adequate in number and
9.
properly spaced . . . . . . . . . . . . . . . . . . . . . . . . .
10.
Water supplies (quantity and pressure)
are adequate . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11.
Fire protection features on piers,
drydocks, POL, etc. have-been included
as applicable . . . . . . . . . . . . . . . . . . . . . . . . . . .
12.
Access roads are adequate...............
All sprinkler heads are properly spaced
13.
with a minimum distance of one (1) foot
from electric light fixtures............
14.
Sprinkler
head locations and fire
detection
elements have been determined
based on
actual site conditions with all
considered . . . . . . . . . . . . . . . . . . . .