ACTUATING CIRCUIT: The CO2 system actuating circuit shall be
3.8
Class A or solenoid coil supervised.
SEALING OF THE AREA: Cable penetrations and trenches shall be
3.9
sealed. The designer shall provide an approved system for sealing openings,
i.e., show a sealing system detail on the contract drawings.
GENERATORS : When generators are protected by gaseous
3.10
extinguishing agents, the designers shall consider wind down time of the
DRAINS : Where floor drains are provided, they are to be deep
3.11
trapped type to prevent leakage of the gas. Drains shall be provided for all
Air Force projects.
PARTITIONS:
Show details of partitions extending down into under
3.12
floor areas.
10
|
||