Share on Google+Share on FacebookShare on LinkedInShare on TwitterShare on DiggShare on Stumble Upon
Custom Search
 
  
 


1.9
AUDIBLE ALARM DEVICES: Audible alarm devices shall be
horns or electronic sound generators.  Use l approximately 3000 ft
2
per audible alarm device in open areas;  Visual alarm indicators shall
be pulse or strobe type.  Provide audiovisual alarms where occupancy
is subject to higher than normal noise or for use by handicapped
personnel.
1.10
SUBMITTALS: Contractor's submittal requirements in
s p e c i f i c a t i o n s shall include a layout plan of all fire alarm devices
and conduit runs in addition to scaled shop drawings required by
NAVFAC Guide Specification 16722.  (Minimum size drawings that are
acceptable is 1/10 scale.)
1.11
RADIO FIRE ALARM TRANSMITTERS and/or
TRANSMITTER/INTERFACE PANEL: Where radio fire alarm transmitters are
r e q u i r e d , the designer shall provide a specification section for
them.  Careful consideration is necessary for placement of radio
transmitters and antenna (obstructions, maximum height allowances,
e t c . ) .  P l a c e in transmitters in accessible, visible, and well
t r a v e l l e d exterior locations.  Combination  transmitter/interface
panels can be used.
1.12
ELEVATORS:  Smoke detectors and/or heat detectors for
elevator machine rooms and hoistway areas shall be controlled by the
building's 24 Vdc FACP.
NOTE: Consult with Code 408 for sequence of operation details
between the elevator controller and the building FACP.
(4)








Western Governors University
 


Privacy Statement - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business