operations involving the storage, mixing, or handling of non-flammable
pesticides a minimum of 100 feet (30.48 m) from the nearest building or
occupied structure.
Exception 1:
Facilities of Type I or Type II - FR construction as
defined by the UBC, may be located less than 100 feet
(30.48 m) from the nearest building or occupied structure,
but not less than 30 feet (9.14 m) in any case.
Exception 2:
Facilities protected by an automatic sprinkler system may
be located less than 100 feet (9.14 m) from the nearest
building or occupied structure, but not less than 30 feet
(9.14 m) in any case.
Exception 3:
Existing facilities involving the storage, mixing, or
handling of non-flammable pesticides are permitted in a
building when all the following are provided:
(a)
The building is completely protected, including the
pesticide area, by an automatic sprinkler system.
(2)
The pesticide area is separated by not less than one-
hour fire rated construction from the remainder of the
building.
(3)
Duct work which penetrates fire rated partitions and
wall assemblies is provided with smoke and fire
dampers.
4.25
Windowless Structures.  Windowless structures are defined in and
shall conform to NFPA 101, Chapter 30.  Windowless structures three stories or
more in height shall also be provided with a manually activated smoke exhaust
system.