10. FIRE PUMPS
(NFGS 15320, NFPA 20)
Must be diesel-powered unless electric power
NDIV 4042, E.1
is supplied from two independent sources.
Controllers must be listed.
(Not custom-built)
NFPA 20, Ch. 7 & 9
Remote-alarms if not in constantly attended
NFPA 20, Paras 7-4.7,
location.
9-4.3
Individual pressure sensing lines for each
NFPA 20, Secs. 7-5.2
controller
and 9-5.2
e
Special anti-corrosion coating for salt
NDIV 4042, E.4
water pumps
11. SMOKE CONTROL SYSTEMS
a
HDBK-1008A, Sec. 4-5.
Is a system required?
Also consult Code 4042
b
Show means of actuation and operating
sequence (detection, dampers, pressurization,
etc.).
C
Show smoke zones/compartments with adequate
partitions.
12. FIRE EXTINGUISHERS
(NFGS 10520N, NFPA 10)
Consult Code 4042
Are cabinets to be provided?
a
b
NFPA 10, Ch. 3
Provide adequate spacing.
Consult Code 4042
Are extinguishers Government or contractor
C
furnished? If contractor furnished,
specify type(s) and UL ratings.