g. Other  special  requirements,  such  as
e. Special load test requirements,
f.  Other
equipment clearances, travel distances for
information/instructions
to
hoists and cranes, etc.,
contractor,
h.North arrow (orient plans so that north is to
g. Abbreviations  and  symbols  used
for
the top or left of the sheet),
structural drawings.
i.  Graphic scales.
2.4.1.2  Foundation Plan:
2.4.1.4  Elevations:
a. Layout of foundation support systems
a. Layout of vertical framing elements showing
showing all dimensions and elevations
all dimensions, orientations and elevations
necessary for construction,
b.Size  or  schedule  references  for  all
necessary for construction,
b.Size or schedule references for all vertical
foundation features such as footings,
framing elements such as column, walls,
grade beams, piles, caissons, pile/caisson
piers, beams, bracing, etc.,
caps, etc.,
c. Wall control/expansion joints,
c. Control/expansion joints in floor slab and
d.Openings requiring special framing or
foundation walls,
reinforcing
d.Trenches,  pits,  openings,  depressed/
e. Location of splices, brackets, penetrations,
thickened slabs,
sleeves, embedments, bracing, weldments,
e. Foundation alternatives,
etc.,
f.  Test pile/caisson location,
f.  Special temporary bracing, shoring or
g. Special construction features - de-watering,
forming,
excavation, bracing, under-pinning, etc.,
g. Other  special  requirements  such  as
h.Special construction sequencing,
equipment, clearances, travel distances for
i.  Existing site conditions/features,
hoists and cranes, etc.,
j.  North arrow (orient plans so that north is
h.Graphic scales.
to the top or left of the sheet),
k.Graphic scales.
2.4.1.5  Sections and Details:
2.4.1.3  Framing Plans:
a. Layout of all sections and details showing all
a. Layout of horizontal framing elements
parts, shapes, sizes, materials, dimensions,
showing all dimensions, orientation and
elevations, arrangement and orientation
elevations necessary for construction,
necessary for construction,
b.Size or schedule references for all horizontal
b.Standard connections or schedule references
framing elements such as beams, joists,
for forces, fasteners, welds, plates, clips,
slabs, decks, grating, etc.,
ties stirrups, pins, etc.,
c. Slab control/expansion joints,
c. All special connections completely detailed
d.Openings requiring special framing or
to a point where no further engineering is
necessary,
reinforcing,
d.Concrete/masonry wall reinforcement details
e. Location of splices, brackets, penetrations,
showing  size,  clearances,  placement,
sleeves, embedments, bracing, weldments,
shape, etc.,
etc.,
e. Lintel details or schedule references for
f.  Special temporary bracing, shoring or
loads, sizes, materials, arrangement, etc.,
forming,
f.  Anchor bolts, base plates, bearing plates,
STRUCTURAL SUBMITTAL REQUIREMENTS