Custom Search
|
|
|
||
P-141, Change 2
May 1996
SECTION 15
MECHANICAL SUBMITTAL REQUIREMENTS
c. Ventilation rates with a statement
1. GENERAL DESIGN GUIDANCE:
Mechanical Systems shall be designed in
regarding compliance with ASHRAE
accordance with criteria outlined in MIL-
Standard 62
d. Discussion of areas to be conditioned and
HDBK-1190, MIL-HDBK-1003/3, SODIV-TG-
1003, Air Force Engineering Technical Letters,
equipment locations/space requirements
e. Documentation of customer's preference
other applicable DM's, Definitive Designs and
criteria as appropriate. Design of the HVAC
for the HVAC control system
f. Information
system for projects that require an energy
on
available
energy
analysis shall not proceed until the alternative
sources/utilities, such as natural gas, steam
selected has been approved by the Code 0733
from central heating plant, chilled water
engineer assigned to the IDR.
from central chiller plant, etc.
g. For projects requiring an energy analysis,
2. SUBMITTAL REQUIREMENTS:
list alternative systems to be analyzed with
a brief statement as to why each system is
2.1 SCHEMATIC SUBMITTAL:
justified for further analysis. Include
The
Exhibit 7-1 from Section 7 of SODIV-
schematic submittal shall consist of the
TG-1003.
following:
h. Any other HVAC design features such as
2.1.1 Basis of Design: The Basis of Design
industrial
ventilation
requirements,
shall be a narrative presentation of facts which
provisions for future heating/cooling plant
will
clearly
indicate
the
selected
additions, etc.
mechanical/plumbing systems and/or the
2.1.1.3 Refrigeration (Cold Storage):
proposed alternative systems to be analyzed. A
discussion and description shall be provided for
Describe refrigeration/cold storage requirements,
the following:
proposed equipment, types of refrigerants, etc.
2.1.1.1
Plumbing Systems:
2.1.1.4 Bulk and Ready Issue Petroleum
Fuel Distribution and Storage:
Discuss
a. Number and types of plumbing fixtures
storage,
distribution,
leak
detection,
b. Selection of piping materials
containment, overfill protection etc.
c. Estimated maximum and minimum water
2.1.1.5 Miscellaneous Mechanical Systems:
pressure
Describe any special mechanical systems such
2.1.1.2 Heating,
Ventilation,
and
Air
Conditioning:
b. Documentation of unusual temperature
and humidity requirements
MECHANICAL SUBMITTAL REQUIREMENTS
15-1
|
||