MIL-HDBK-419A
Table 5-3
DC Parameters of Some Standard Cables
Diameter
Size
(Ohms/1000 ft)
(AWG)
(mils)
No. 1 2
80.81
1.588
No. 8
128.5
0.6282
No. 2
257.6
0.1563
1/0
324.9
0.09827
Table 5-4
Sixty-Hertz Characteristics of Standard Cables
Size
Length
(AWG)
(Ft)
No. 12
30
16.532
0.00623
0.0480
0.04764
0.02354
0.1605
No. 12
100
0.15880
62.447
0.00591
0.0197
30
0.01885
15.684
No. 8
0.0072
0.00469
14.411
0.00543
No. 2
30
0.02088
0.0261
No. 2
100
0.01563
55.379
0.0402
0.02344
86.777
0.03271
No. 2
150
0.0060
13.987
0.00527
30
0.00294
1/0
0.0060
53.964
0.0226
100
0.00980
1/0
0.0351
150
0.01470
84.654
0.03191
1/0
0.0746
181.987
0.06861
300
0.02940
1/0
0.1158
284.105
0.10710
450
0.04410
1/0
5-11