Table 15-3. Interior wiring and lighting system.
CHECK
REF.
RESPONSIBILITY
Each scheduled
Unauthorized or nonstandard attachments
Maintenance Group
(Operator/
building visit
Defective convenience outlets and switches.
Electricians
Improper cords.
5-4-4
Proper fuse sizes in panels.
Overheating of panels.
Any condition likely to cause fire. Check battery-
type emergency lights and replacement lamps.
9-7
Check for Iamps larger than standard prescribed
for outlet.
9-6
Replace burnt out lamps in hard-to-reach places.
(To be accomplished by electrical shop if special
equipment such as ladder trucks are needed).
5-4-1
User
AS Required
Panels for circuit idenificaton and accessibility.
5-4-4
Replace blown fuses.
9-6
Replace burnt out or defective incandescent lamps.
9-6
Replace burnt out fluorescent lamps if personnel
have been instructed in this function and if assigned
to user. Promptly replace or report defective
lamps since a lamp approaching bum out flashes on
and off, causing overduty on auxiliary equipment.
Make repairs and adjustments to systems when
Electrician
As required.
malfunctions are reported. Ensure that all work
complies with the NEC
14-5
Check ground resistance for special weapons
Electrician
As required.
facilities at request of user.
13-2
Check for low voltages and/or low power factor.
Electrician
Monthly or
Inspect station (substation switchgear or UPS) as
Annually
follows:
2-8-3
(1) Check electrolyte level and add distilled water if
needed.
(2) Check charging rate. Adjust charging rate as
necessary to maintain proper specific gravity.
(3) Test for proper operation under simulated
power interruption. Check maintenance free
batteries. Check voltage, check and clean
terrminal/connection.
15-3
|
||