Share on Google+Share on FacebookShare on LinkedInShare on TwitterShare on DiggShare on Stumble Upon
Custom Search
 
  
 


Table 15-3. Interior wiring and lighting system-continued.
REF.
CHECK
RESPONSIBILITY
Electrician
As required
Infrared scan, if available, and inspect
buildings for defective wiring and loose
connections. Tighten or replace, as
necessary. Check grounds for continuity.
Check all systems for abnormal conditions.
14-4
Correct discrepancies.
Inspect disconnects, cabinets, panels and load
centers. Tighten connectionss. Clean panels.
chapter
Check fuse sizes. Manually operate switches
5
and breakers.
Use ohmmeter to detect grounds. Eliminate
13-2
defects.
Check and correct unbalance of loads
chapter
Clean transformers, ducts and capacitors.
3, 24,
2-8-2.
Electrician
As required
Clean lighting fixtures whenever foot-candle
readings drop 20 to 25%. This will beat
approximate ly annual intervals in ordinary
offices, longer in clean rooms, and at lesser
intervals for dirty areas. Work should be
accomplished by custodial or by user if
within capabilities.
9-5
Electrician
Every Year
Test power circuit breakers and protective
2-8-8
Test metering and indicating instruments
2-8-4, 2-
8-5, 2-8-
7
Electrical Shop
Every 5 years
Test molded case feeder and main circuit
543
breakers in main panelboards.
Test single phase watt hour meters.
2-8-5
15-4








Western Governors University
 