Share on Google+Share on FacebookShare on LinkedInShare on TwitterShare on DiggShare on Stumble Upon
Custom Search
 
  
 


STRUCTURAL
5.2 STRUCTURAL INSPECTION INSTRUCTIONS:
5.2.1 Aircraft Power Check Facility: Comply with all current safety precautions.
Check For:
n Aircraft Securing Fittings and Mooring Eyes:
cracked, broken or spalled concrete
settlement, movement or heave in vicinity of fittings
rusted, loose, bent or broken anchor plates and bolts
n Chain:
breakage, rust, corrosion and wear between individual links and
between links and fittings
check chain dimensions for distortion in accordance with
NAVSHIPS 0901-260-0001
Aircraft Holdback and Deck Fittings:
rust
corrosion
bent, worn or damaged parts
Blast Deflectors:
rust
corrosion
bent, missing or damaged parts
5.2.2 Ammunition Storage (Aboveground): Comply with all current safety
precautions. Check for:
n  Main, Foundation, and Retaining Walls:
Cracks
Spalling
Broken areas
Settlement
Failure to maintain 3 ft minimum earthfill width at tops of retaining
walls and minimum side slope of 1-1/2 to 1 at earth embankments
Drainage problems resulting in surface ponding or other evidence
of subsurface draining failure