MECHANICAL
Water Utility System-Continued
Valve box wetness
Line leaks
Proper operation of
Wells
Pumps
Proper operation of chlorination plant (check with the operator
about problems)
6.3 REPAIR/REPLACEMENT CRITERIA:
6.3.1 Air conditioning -
n Chillers:
Repair
General good condition
Only specific parts require replacement or repair
Parts are easy to procure
Replacing or repairing parts is cost effective
Replacement
Over 20 years old
Badly rusted, damaged, deteriorated
Leaking refrigerant or oil (indications of frequent or
continuous leaks)
Many breakdowns and repairs (check activity record)
Parts difficult or impossible to procure
Replacing or repairing parts is not cost effective
n Cooling towers:
Repair - Only minor repairs required
Replacement
Over 15 years old
Many or severe leaks
Heavy corrosion and deterioration
n
Controls (electric/pneumatic):
6-44