Fire Pump Houses: All fire pump houses shall be
5.5.3
constructed of noncombustible construction. Diesel driven pump houses
s h a l l be sprinklered.
5.6
DUAL DRIVEN FIRE PUMPS: No dual driven fire pumps shall
be used.
5.7
SALTWATER SYSTEMS: Saltwater systems shall be installed
f o r ships in cold iron. I n other locations consider salt water
systems on a case-by-case basis (per NAVFAC).
5.8
AUTOMATICALLY ACTUATED FIRE PUMPS: All fire pumps shall
be automatically actuated via pressure drop and manually started at
the fire pump controller. Remote automatic start shall be provided
f o r aircraft hangars. A l l fire pumps shall be manually stopped, i.e.,
automatic stop or manual remote stop is prohibited.