MIL-HDBK-1008B
APPENDIX D (Continued)
TABLE D1
WATER DEMANDS FOR UNSPRINKLERED FACILITIES
TOTAL WEIGHTED VALUE
Occupancy Hazard
Fire Flows
Duration
Classification
(gpm at 20 psi
(minutes)
residual pressure)
 6-10 11-15
16+    6-10  11-15    16+
Light
 750    1125  1500  
60  
90
 120
Ordinary Group 1
 1000  1500  2000  
90  
120
 150
Ordinary Group 2
 1500  2250  3000  
90  
120
 150
Extra
 2500  3750  5000  
150
195
 240
70