Share on Google+Share on FacebookShare on LinkedInShare on TwitterShare on DiggShare on Stumble Upon
Custom Search
 
  
 


MIL-HDBK-1008B
APPENDIX D (Continued)
D.
Examples Calculations
(1)
Administration Office Building (Light Hazard)
Factors
Values
1.
Fire department response
1
On-site (within 1 mile)
2.
Type of Construction:
2
Type II
3.
Number of Stories:
2
Two stories
4.
Separation Distance:
2
30 feet
5.
Building Floor Area:
3
22,000 square feet
6.
2
170 feet
---
Total Weighing Value
12
Per Table D1:
1125 gpm for 90 minutes
(2)
Welding Shop (Ordinary Group 1)
Factors
Values
1.
Fire department response
2
Off-site (within 2 mile)
2.
Type of Construction:
3
Type II
3.
Number of Stories:
1
Single story
4.
Separation Distance:
4
20 feet
5.
Building Floor Area:
3
22,000 square feet
6.
4
250 feet
---
Total Weighing Value
17
Per Table D1:
2000 gpm for 150 minutes
(3)
Barracks (Light Hazard)
71