FIRE PROTECTION DESIGN CHECKLIST
Reference
CONSTRUCTION AND INTERIOR FINISH
1.
a
Provide description of function(s) to be/being
UBC, Table 5-A
performed in the building.
HDBK 100BA, App. A
b
Classify building occupancy Group(s) and
UBC Table 5-A
Division(s) per UBC.
C
State gross floor area and height of building
d
Determine building Construction Type and Sub-
UBC, Table S-C
Type per UBC, based on the allowable height
Ch 17-22
and area for the occupancy. Apply allowable
Sec. 505, 506
area or height increases as appropriate (from
separation distances, sprinkler protection, etc,
per UBC). Show hourly ratings of all fire rated
assemblies on drawings. Indicate on drawings
UL, FM, or other nationally recognized testing
laboratory approved assembly reference number(s)
to allow NORTHDIV to verify the fire rating of
the assemblies.
e
For existing buildings, state Construction Type
UBC, Table 5C
and Sub-Type, determined from UBC based on
Ch 17-22
actual construction of building.
For renovations or additions to an existing
UBC, Table 5C
building, is occupancy permitted in that con-
Sec 505, 506
struction type? Will final height and area be
within UBC limits for the type of construction
and occupancy? If not, explain in detail re-
medial actions proposed to bring the finished
building into compliance with the Code.
UXC, Table S-B
If a building is of mixed occupancy, is re-
NFPA 101 Ch 6
quired interior separation provided per UBC
and NFPA 101? Show hourly ratings of all
fire rated assemblies on drawings. Indicate
on drawings UL, FM, or other nationally re-
cognized testing laboratory approved assembly
reference number(s).