7.10 SUMMARY OF GUIDELINES.
Bonds must be designed into the system.
Specific attention should be directed to the
l
interconnections not only in power lines and signal lines, but also between conductors of signal
ground bus networks, between equipments and the ground bus networks, between both cable and
component or compartment shields and the ground reference plane, between structural members,
and between elements of the lightning protection network. In the design and construction of a
considered along with mechanical and operational needs.
l
hold the surfaces in contact in the presence of the deforming stresses, shocks, and vibrations
associated with the equipment and its environment.
l
currents flowing through it, and the environmental conditions to which it is subjected.
o
Bonding jumpers are only a substitute for direct bonds. If the jumpers are kept as short as possible,
have a low resistance and low
ratio, and are not higher in the electrochemical series than the
bonded members, they can be considered a reasonable substitute.
Bonds are always best made by joining similar metals. If this is not possible, special attention must
l
be paid to the control of bond corrosion through the choice of the materials to be bonded, the
selection of supplementary components (such as washers) to assure that corrosion will affect
Protection of the bond from moisture and other corrosive elements must be provided.
o
Finally, throughout the lifetime of the equipment, system, or facility, the bonds must be inspected,
l
tested, and maintained to assure that they continue to perform as required.
7-36
|
||