Share on Google+Share on FacebookShare on LinkedInShare on TwitterShare on DiggShare on Stumble Upon
Custom Search
 
  
 


MIL-HDBK-419A
(2)
Following the manufacturer's instruction, obtain a resistance reading, R, with the test set.
(3)
Convert the probe spacing, A, to centimeters. (See Page xvi for metric conversion factors.)
(4)
Compute resistivity from
(in ohm-cm)
= 6.26AR
(1-1)
Assume that a resistance of 2 ohms is measured with probe spacings of 20 feet.
EXAMPLE:
Convert 20 feet to centimeters: 20 f t x 30.5 cm/ft = 610 cm
Calculate resistivity:
= 6.25 x 610 x 2 = 7662 ohm -cm
A = ELECTRODE SPACING
B = DEPTH OF PENETRATION < A / 2 0
D = DEPTH AT WHICH RESISTIVITY IS DETERMINED = A
Figure 1-1. Measurement of Soil Resistivity
1-3








Western Governors University
 


Privacy Statement - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business