MIL-HDBK-419A
EARTH
NOTES: 1. WHEN CABLE HAS OUTER ARMOR SHIELD, CONNECT THE
ELECTRODE
ARMOR TO THE GROUND BUS BAR. ALSO, ELECTRICALLY
BUILDING
SUBSYSTEM
CONNECT TWINAXIAL CABLE SHIELD TO GROUND BUS BAR.
PENETRATION
2. USE 2 SERIES-CONNECTED AVALANCHE DIODES WHEN LIN E
VOLTAGE > 12V.
3. STANDOFF VOLTAGE FOR TS2 SHOULD BE AS LOW AS
POSSIBLE, BUT SHALL NOT TURN ON IN RESPONSE TO
HUM VOLTAGE ON SHIELD.
B. TYPICAL TRANSIENT SUPPRESSION FOR
4. J-BOX SHALL BE GROUNDED USING SHORTEST MEANS.
COAXIAL CABLES (COAXIAL SHIELD ISO-
LATED FROM GROUND)
Figure 1-44. Transient Suppression for Coaxial Lines (DC To 3 MHz)
1-95