Figure 3-8. Grounding of Overall Cable Shields to Penetrated Walls
3.2.1.2 Higher Frequency Equipment. In higher frequency equipments, multiple-point equipotential grounding
is required. The various signal pairs internal to the equipment are referenced as required to a metallic common
or equipotential ground plane with minimum length conductors. The equipment chassis is normally used as the
signal reference plane. The equipment chassis is grounded through the case or cabinet to the equipotential
ground plane. Yellow covered wire or cable of adequate size should be employed for all interconnections of the
higher frequency signal reference network.
3-12