3) A fire alarm riser and suppression
equipment is required. Ensure the power
supply and point of connection to base
system
diagram
showing
the
wide fire alarm is shown.  (Note:
interconnection of all fire alarm
Source of power to fire alarm control
panel shall be taken prior to the main
power disconnect.)
4) Emergency lighting locations shall be
provided on the electrical floor plan with
a detail of each type of emergency light
fixture provided.
5) The fire alarm zone, suppression, and
annunciation schedule shall be detailed.
Complex fire alarm systems such as jet
engine test cells and hush houses,
Aircraft Hangars, etc. shall require a
chart detailing a sequence of operations.
6) Fire  stop  details  of  electrical
penetrations of fire wall with a note
referring to the appropriate architectural
sheet for fire wall location.
2.5  FINAL SUBMITTAL:
The final
submittal shall incorporate the corrections and
comments noted on the 100% submittal and be
ready
for
signature
by
the
SOUTHNAVFACENGCOM Fire Protection
Engineer.
FIRE PROTECTION SUBMITTAL REQUIREMENTS
16-4