SECTION 17
ELECTRICAL SUBMITTAL REQUIREMENTS
1. DESIGN GUIDANCE:
conditions should be
complete and field
checked.
1.1  GENERAL:  Designs utilizing sound
c. Single Line Diagram: This plan should
engineering judgment supported by detailed
show the following:
calculations are required.
All engineering
1) Existing distribution to a point of
decisions must be documented.
connection.
1.2  CRITERIA: Follow SODIV-TG-1004,
2) Primary feeder to project.
3) Padmounted transformer or substation
"Technical Guidance for Electrical Design"
(formerly SOUTHDIV 16000).  Use other
with primary and secondary switchgear.
4) Secondary feeders.
criteria as required by facility type (refer to
SOUTHNAVFACENGCOM 00001 "Index of
2.1.2
Schematic Basis of Design:
Criteria").
2. SUBMITTAL REQUIREMENTS:
a. Primary Distribution:
1) Describe the primary source of power.
2.1  SCHEMATIC SUBMITTAL:
2) Where the source of power is located.
The
3) Statement relative to the adequacy of
Schematic Submittal shall include the following:
the primary supply at the point of take-
a. Electrical Drawings
off.
b.Basis of Design
4) Electrical  characteristics  of  power
supply to station, or portion involved,
2.1.1
Schematic Electrical Drawings:
including circuit interrupting and voltage
regulation requirements.
a. Existing Site and Demolition Plan: This
5) Estimate of total connected load and
plan should include all existing site information
resulting KVA demand load by applying
such as buildings, pavements and utilities. All
proper  demand  (state  operating
electrical demolition should be shown on this
assumptions) and diversity factors.
6) Basis for selection of secondary voltage.
drawing and indicated by legend. Demolished
7) Distribution, overhead or underground.
features should not be shown on subsequent
8) Type of conductors, such as copper or
drawings.
aluminum.
b.Site Plan: This plan should show new and
9) Type of conduit or duct if used.
10) A  statement  describing  pertinent
remaining aboveground and underground
electrical equipment.
When located in
standards of design, such as voltage
proximity to other utilities, all should be shown
drop,  physical  characteristics  of
to avoid conflicts. Information on existing
overhead  or  underground  circuits,
clearances, etc.
ELECTRICAL SUBMITTAL REQUIREMENTS